Site Transformer 10kVA 230V-110V
- Air cooled
- Heavy-duty steel enclosure
- Double wound with safety earth screen
- MCB protection against overload
- Manufactured to BS (EN) 61558-2-23
Features
- The 110V transformer is for use on building sites to provide a reduced voltage.
- 40 amp input screw terminal block
- 4 x 16 amp outlet sockets
- 2 x 32 amp outlet sockets
- CTE (Centre tap to earth)
- Fitted with 5 MCBs (Miniature circuit breakers)
- One MCB on the input, two on the 16 amp outlets one on each 32 amp outlet
- Constructed with a robust heavy duty site case and housed under a weatherproof cover.
- Climatic class outdoor use
| Specifications | |
| Intermittent or Tool Rating | Single phase 10,000VA @ 50/60HZ |
| Continuous Rating | 10,000 VA |
| Input | 230 v @ 43.48 amps |
| Output | 4 x 110V CTE with IP44 16 amp panel mounting sockets with weatherproof covers |
| Output | 2 x 110V CTE @ 90.91 amps with IP44 32 amp panel mounting sockets with weatherproof covers |
| Input Protection | 1 x 40 amp 2 pole type DMCB |
| Output Protection | 2 x 16 amp 2 pole type C MCB + 2 x 32 amp 2 pole type C MCB |
| Tripping Characteristics | European standard EN60898 (-25 deg C - +55 deg C) |
| Earthing | Earth screen between primary and secondary windings |
| Insulation | Thermal insulation Class E. Maximum 120 deg C |
| Temperature Rise | 75 deg C. Maximum 80 deg C |
| Feeder Cable Size | Up to 30m 6mm or 60m 10mm |
| Enclosure | Sheet steel ventilation drip proof IP40 + IP44 Weatherproof covers over MCBs |
| Dimensions | H 590mm (inc. handles 640mm) x W 365mm(inc. handles 430mm) x D 440mm |
| Weight | 73 kg |